Whenever the NIRC2 #2 cold head temperature goes above its set point by approximately 5 degrees (i.e., increases from 50K to 55K), the auto-pump system will kick on. As of this writing, this event has occurred only on those occasions when the CCR system becomes unavailable for approximately two hours or more (typically due to difficulties with the facility glycol system).
The following procedure should be followed once temperatures have returned to their nominal values (in particular, thead2hi is again 50K and controlling close to that level). Note that there is no particular rush to return the system to its nominal (i.e., solenoid valve closed and turbo-pump off) state, however, ideally, it should be followed within a few hours after the cryo system is stable for at least two reasons:
Procedure:
ad 5 "ALARMST?_B". The value will read
1,0 (see caveat below) if the
system is in the over-temp (pump-on) state.
snaptemps to record the state of the cryo system
and save the file in your records for later.
td 5
"ALMRST".
snaptemp measurements.
There has been much confusion about the meaning of the return
from the ad 5 "ALARMST?_B". As of this writing
(August 22, 2010), we are fairly certain that:
0,0 => No alarms on 1,0 => High temp alarm (pump on until reset) 0,1 => Low temp alarm (no action required) 1,1 => Both alarms on
In particular, on August 22, 2010 the returned value
was 0,1 and:
nirc2dewar.watch returned "OK"